AACULP - Unité de Contrôle pour le Câble Analogique LHD Alarmline II - Alarmline II Analogue LHD Control UnitAACULP - Unité de Contrôle pour le Câble Analogique LHD Alarmline II - Alarmline II Analogue LHD Control Unit
Print

Alarmline II Analogue LHD Control Unit AACULP

Control Unit - PC Programmable for Analogue Linear Heat Detection (LHD) cable Alarmline II - AACULP - ProReact A1163
956,00 €
Total without tax: 956,00 €
Description

AACULP - Alarmline II Analogue LHD Control Unit - PC Programmable

The AACULP is a PC programmable, Analogue Linear Heat Detection (LHD) cable control unit. It provides monitoring for any of the Alarmline II range of LHD sensor cable, configuration of alarm and pre-alarm temperatures as well as enabling simple interface to a main fire alarm or BMS system.

Interface & Programming
The AACULP provides LED indications only and requires a PC to configure the control unit.
Pre-Alarm and Alarm thresholds can be set through simple menu options with no need for any graphs or nomograms. Initial set-up is done by measuring and entering the calibration resistance of the sensor cable removing the need to know the sensor cable length.
Volt free changeover contacts are provided inside the control unit for Pre-Alarm and Alarm signaling to a main fire alarm control panel or BMS system. A failsafe opto-isolated phototransistor fault output is also provided.
No user controls are provided on the control unit. An isolated input is provided enabling remote reset functionality.

Operation
As well as monitoring the LHD sensor cable for changes in temperature, the control unit also monitors for open and short circuit faults along the cable ensuring notification if the cable becomes
damaged.It is fitted with its own internal temperature monitor and should the temperature within the controller enclosure reach 100°C (212°F), an alarm will be signaled.
Each control unit may have up to 500m (1640ft) of LHD sensor cable connected to it, acting as a single detection zone. When the LHD sensor cable and the control unit are installed in different areas, a suitable interposing cable can be used to make the electrical connection between them.

FEATURES & BENEFITS

  Other Reference : ProReact A1163

Alarmline II Analogue LHD Control Unit AACUSPAlarmline II Analogue LHD Cable w/ PVC Sheath AA-0500
Back to: Linear Heat Detection