Reflective Optical Beam Smoke Detector 100m FR100R
Reflective Optical Beam Smoke Detector 50 to 100m range FIRERAY FR100R Fire Fighting Enterprises
FR100R - Reflective Optical Beam Smoke Detector 50 to 100m range FIRERAY
The FIRERAY 100R conventional infrared optical beam smoke detectors provide economical and effective protection of large, open plan spaces with high ceilings, particularly if access to 'point type' smoke detectors presents practical difficulties.
Optical beam smoke detectors are ideally suited for protecting warehouses, factories, atria, shopping malls, leisure centres, churches,museums, power stations and industrial plants.
The FIRERAY 100R optical beam smoke detectors can be connected to a zone of a conventional fire alarm control panel, or interfaced to an analogue addressable system via an addressable interface input module or a zone monitor module.
FEATURES & BENEFITS
- Combined transmitter and receiver unit in one discrete unit
- Range 50-100 Metres
- Low current consumption
- Automatic self check drift compensation
- Selectable sensitivity/threshold levels
- Selectable latching / non latching fire alarm
- LED indicators to aid the alignment process
- Optional Low Level Test Unit for UL models only
TECHNICAL SPECIFICATIONS
- Operating Range : 50 to 100 Metres
- Operating Voltage Range : 10.2V DC to 30Vdc
- Quiescent Current :
- Alarm Current : <15mA
- Power Down Reset Time : 5 seconds
- Fire Relay Contacts : Normally Open,VFCO 2A @ 30Volts DC, resistive
- Fault Relay Contacts : Normally Closed,VFCO 2A @ 30Volts DC, resistive
- Operating Temperature : -20°C to +55°C (non-condensing)
- Fire Alarm Thresholds : 1.25dB (25%), 1.87dB (35%), 3.00dB (50%)
- OpticalWavelength : 880nm
- Detector Dimensions : Width 126mm, Height 210mm, Depth 120m
- Prism Dimensions : Width 100mm, Height 100mm, Depth 9.5mm
- Weight : 0.67 kg
- LED Indications : Red LED: Indicates FIRE, Continous Amber LED: Indicates FAULT, Flashing Amber LED: Once every 10 seconds indicates normal operating mode (RV Models only), Flashing Amber LED: Once every 2 seconds indicates the compensation function has reached its limit
- Alarm Condition : Indicated by fire relay closing, Alarm may be latching or non-latching (default)
- Fault Condition : Indicated by fault relay opening
- IP Rating : IP50
- Relative Humidity : RH 0% to 93%, (non-condensing)
- Approvals/Certification : Designed, manufactured and certified to EN54-12: 2002, Use 25% and 35% (default) thresholds.The 50% threshold is recommended for hostile and extreme environments.
- CPD Reference : 0786-CPD-20045
- UL File : S3417
- Parts List : 1 x Detector Head Assembly, 4 x prism, 1 x Test Filter, 1 x Cable Interface
- Housing Construction : Flame Retardant ABS, Finish: Grey / Black
-
Recently Viewed
Additionnal Head Optical Beam Smoke Detector 50m FR5000 EN54 - 5000-002 - FFE
Integrated UV/IR Flame Detector Explosion Proof enclosure 40/40C-LB for hydrocarbon-based fuel fires and non-organic fires SharpEye Spectrex
Iso Butyl Alcohol Gas Detector - Explosion Proof Enclosure Version S2157IT
Iso Butyl Alcohol Gas Detector, Isobutanol Gas Detector 0-100% LFL 4-20mA - Catalytic sensor - SMART3G-D2 Sensitron Explosion Proof Enclosure Version with display Zone 1 category 2 areas S2157IT
R1234ze Gas Detector SMART3-H LITE S3845R1234ZE
R-1234ze refrigerant Gas Detector, HFO-1234ze Gas Detector 0-20% LFL - Infrared sensor - SMART3-H LITE for non classified area S3845R1234ze - Sensitron
Duct Mount for 40/40C,D series Flame Detector 877670 SharpEye SPECTREX
Hydrogen Gas Detector - Explosion Proof Enclosure Version S2097H2
Hydrogen Gas Detector 0-100% LFL 4-20mA - Catalytic sensor - SMART3G-C2 Sensitron Explosion Proof Enclosure version Zone 1 category 2 areas S2097H2
Digital Linear Heat Detection (LHD) cable 105°C (221°F) with PVC Sheath PROLINE - TH105
R1234yf Gas Detector SMART3-H-FM LITE S4144R1234YF
R-1234yf refrigerant Gas Detector, HFO-1234yf Gas Detector 0-20% LFL 90-240 Vac - Infrared sensor - SMART3-H-FM LITE for non classified area S4144R1234YF - Sensitron
Ammonia Gas Detector - Dust Proof Enclosure Version S2164AM
(NH3) Ammonia Gas Detector, Azane Gas Detector, Hydrogen nitride Gas Detector 0-200 ppm 4-20mA - Electrochemical cell - SMART3G-D3 Sensitron Dust Proof Enclosure Version with display Zone 2 category 3 areas S2164AM
256 zones SIL2 Gas Control Panel Multiscan S2 STMTSS2-256B
256 zones Gas Control Panel ATEX and SIL2 ABS housing Multiscan++S2 Sensitron STMTS/S2-256B
English (UK)
Français (FR)