4 Zones Fire Detection Alarm System Panel SIGMA K11040M2
4 Zones Conventional Fire Detection Alarm System Panel SIGMA CP K11 Kentec K11040M2
K11040M2 - 4 Zones Conventional Fire Detection Systems Panel Sigma CP K11 Kentec
The Sigma CP range consists of a series of conventional fire detection systems panel designed in accordance with European standards BS EN54-2 and BS EN54-4 Fire Detection systems - Control and Indicating Equipment.
The range consists of 2, 4 and 8 zones fire detection alarm system panel.
Sigma K11 range in which detectors and call points are wired on separate circuits to sounders (two sounder circuits are provided).
All fire detection alarm systems panel have an integral, mains powered battery charger and power supply designed in accordance with the requirements of BS EN54-4.
FEATURES & BENEFITS
- Fully certified to BS EN54-2 and BS EN54-4
- Versions in 2, 4 or 8 zones
- Compatible for use on BS5839: Part 1: 2002 installations
- 2-wire repeaters and ancillary boards
- Fully programmable using simple menu options
- Adjustable sounder delay time
- Sounder configuration options
- Zonal sounder delay detectors only
- Zonal sounder delay call points only
- Coincidence input selection
- I.S Barrier selection by zone
- Short circuit fire by zone
- Non latching zones
- Silent zones
- Zone input delay
- General panel configuration
- Simple, single board construction
- Installer friendly
- Compatible with wide range of fire detection devices
- Two monitored sounder outputs
- 3 Amp power supply
- Auxiliary power output
TECHNICAL SPECIFICATIONS
- Construction : 1.2 mm mild sheet steel
- Finish : Epoxy powder coated
- Colour - lid & box : BS 00 A 05 grey - fine texture
- Colour - control plate & labels : RAL 7047 light grey - satin
- Supply voltage : 230 VAC (+10%/-15%)
- Mains supply fuse : 1.6 A 250V
- Power supply DC rating : 24V 3A
- Maximum battery size : 7Ah 12V (2 per panel)
- Fault contact rating : 30 VDC 1A
- Local fire contact rating : 30 VDC 1A
- Fire contact rating : 30 VDC 1A
- Sounder output rating : 0.5A per output (Max 1.6A over all outputs)
- Detection zone current : 1.6 mA
- Detection zone EOL resistor : 6K8 5%
- Active EOL : K14606K (optional)
- Sounder output EOL resistor : 10K 5%
- Cable capacity : 2.5 mm©
- Operating temperature : -5°C a +50°C
- Operating humidity : < 95% (non condensing)
- Dimension : 385 mm x 310 mm x 90 mm
- Standby current 2 zones : 0.065 A
- Standby current 4 zones : 0.075 A
- Standby current 8 zones : 0.093 A
- Alarm current 2 zones : 0.10 A
- Alarm current 4 zones : 0.21 A
- Alarm current 8 zones : 0.55 A
Recently Viewed
Fire sounder, hazardous area, multi tone, horn AS374
Fire sounder, ATEX hazardous area, 32 Tones user selectable, horn, IP67 Marine grade housing - AS374 UTC Fire & Security
Dual IR flame detector in Eexd - IIC T6 flame proof housing Talentum-16511-00
Dual IR flame detector in Eexd - IIC T6 flame proof housing EN54-10 Talentum-16511-00
FAAST-LT Stand Alone - 2 channel with 2 laser detectors FL0122E
Stand Alone Aspirating Smoke Detector 2 channel with 2 laser detectors (separated chambers) FAAST-LT FL0122E System Sensor
Transmitter Exd SIL2 Aluminum enclosure LCD SSS4A13
Transmitter Exd SIL2 Aluminum enclosure, 4 entries, copper free, Electronic with1 output RS+4-20mA, LCD display, relay card - Zone 1 areas SMART S-SS SSS4A13 Sensitron
2MPX HD IP Wedge Dome camera 4mm lens IP66 TVD-M2210W-4-P
2MPX Full HD Wedge Dome Network Camera, 4 mm fixed lens, IP66, TVD-M2210W-4-P - UTC Fire & Security
Intrinsically Safe Conventional Photoelectric Smoke Detector SLR-E-IS/SIL
Intrinsically Safe Conventional Photoelectric Smoke Detector, SIL2 approved SLR-E-IS/SIL - Hochiki
English (UK)
Français (FR)