2 Zones Fire Detection Alarm System Panel SIGMA K11020M2
2 Zones Conventional Fire Detection Alarm System Panel SIGMA CP K11 Kentec K11020M2
K11020M2 - 2 Zones Conventional Fire Detection Alarm System Panel Sigma CP K11 Kentec
The Sigma CP range consists of a series of conventional fire detection alarm system panel designed in accordance with European standards BS EN54-2 and BS EN54-4 Fire Detection and Fire Alarm systems - Control and Indicating Equipment.
The range consists of 2, 4 and 8 zones fire detection alarm system panel.
Sigma K11 range in which detectors and call points are wired on separate circuits to sounders (two sounder circuits are provided).
All fire detection alarm system panel have an integral, mains powered battery charger and power supply designed in accordance with the requirements of BS EN54-4.
FEATURES & BENEFITS
- Fully certified to BS EN54-2 and BS EN54-4
- Versions in 2, 4 or 8 zones
- Compatible for use on BS5839: Part 1: 2002 installations
- 2-wire repeaters and ancillary boards
- Fully programmable using simple menu options
- Adjustable sounder delay time
- Sounder configuration options
- Zonal sounder delay detectors only
- Zonal sounder delay call points only
- Coincidence input selection
- I.S Barrier selection by zone
- Short circuit fire by zone
- Non latching zones
- Silent zones
- Zone input delay
- General panel configuration
- Simple, single board construction
- Installer friendly
- Compatible with wide range of fire detection devices
- Two monitored sounder outputs
- 3 Amp power supply
- Auxiliary power output
TECHNICAL SPECIFICATIONS
- Construction : 1.2 mm mild sheet steel
- Finish : Epoxy powder coated
- Colour - lid & box : BS 00 A 05 grey - fine texture
- Colour - control plate & labels : RAL 7047 light grey - satin
- Supply voltage : 230 VAC (+10%/-15%)
- Mains supply fuse : 1.6 A 250V
- Power supply DC rating : 24V 3A
- Maximum battery size : 7Ah 12V (2 per panel)
- Fault contact rating : 30 VDC 1A
- Local fire contact rating : 30 VDC 1A
- Fire contact rating : 30 VDC 1A
- Sounder output rating : 0.5A per output (Max 1.6A over all outputs)
- Detection zone current : 1.6 mA
- Detection zone EOL resistor : 6K8 5%
- Active EOL : K14606K (optional)
- Sounder output EOL resistor : 10K 5%
- Cable capacity : 2.5 mm©
- Operating temperature : -5°C a +50°C
- Operating humidity : < 95% (non condensing)
- Dimension : 385 mm x 310 mm x 90 mm
- Standby current 2 zones : 0.065 A
- Standby current 4 zones : 0.075 A
- Standby current 8 zones : 0.093 A
- Alarm current 2 zones : 0.10 A
- Alarm current 4 zones : 0.21 A
- Alarm current 8 zones : 0.55 A
Recently Viewed
BUTANE Gas Detector - Dust Proof Enclosure Version S2096BU
Butane Gas Detector 0-100% LFL 4-20mA - Catalytic sensorl - SMART3G-C3 Sensitron Dust Proof Enclosure Version Zone 2 category 3 areas S2096BU
Additionnal Head Optical Beam Smoke Detector 50m FR5000 NF - 5000-048 - FFE
Alarmline II Digital LHD Cable 88°C (190°F) w/ PP Sheath AD88P-1000
Digital Linear Heat Detection (LHD) cable 88°C (190°F) with Polypropylene Sheath Alarmline II, 1000m - AD88P-1000 - ProReact F1076
R1234YF Gas Detector SMART3-H-FM LITE S4692R1234YF
R-1234yf refrigerant Gas Detector, HFO-1234yf Gas Detector 0-5000 ppm 12-24 Vdc - Infrared sensor - SMART3-H-FM LITE for non classified area S4692R1234YF Sensitron
VOC Gas Detector (Benzene) 0-100 ppm Gas Detector - Dust Proof Enclosure Version S5024BZ
Volatile Organic Compound Detector, VOC Detector 0-100 ppm (Benzene) 4-20mA - PID sensor SMART3G-C3 Sensitron Dust Proof Enclosure Version Zone 2 category 3 areas S5024BZ
Outdoor siren with single amber beacon - polycarbonate cover AS610 UTC Fire & Security Aritech
Complete set 7º OSID smoke detector OSI-10-K
Complete set with 7º OSID smoke detector and wireless transmitter for a distance of 30 to 150 Meter - OSI-10-K - XTRALIS
Standard Mounting Base ECO1000B
ECO1000 Series Standard Mounting Base for Detector ECO1000B System Sensor, Morley-IAS
Analogue Multi-Sensor ACC-EN/SIL
Analogue Multi-Sensor Photoelectric/Heat, Ivory case, SIL2 Approved ACC-EN/SIL Hochiki
IR Flame Detector - Explosion proof enclosure RIV-601P/FA Control Logic
English (UK)
Français (FR)