Alarmline II Analogue LHD Control Unit AACULP
Control Unit - PC Programmable for Analogue Linear Heat Detection (LHD) cable Alarmline II - AACULP - ProReact A1163
AACULP - Alarmline II Analogue LHD Control Unit - PC Programmable
The AACULP is a PC programmable, Analogue Linear Heat Detection (LHD) cable control unit. It provides monitoring for any of the Alarmline II range of LHD sensor cable, configuration of alarm and pre-alarm temperatures as well as enabling simple interface to a main fire alarm or BMS system.
Interface & Programming
The AACULP provides LED indications only and requires a PC to configure the control unit.
Pre-Alarm and Alarm thresholds can be set through simple menu options with no need for any graphs or nomograms. Initial set-up is done by measuring and entering the calibration resistance of the sensor cable removing the need to know the sensor cable length.
Volt free changeover contacts are provided inside the control unit for Pre-Alarm and Alarm signaling to a main fire alarm control panel or BMS system. A failsafe opto-isolated phototransistor fault output is also provided.
No user controls are provided on the control unit. An isolated input is provided enabling remote reset functionality.
Operation
As well as monitoring the LHD sensor cable for changes in temperature, the control unit also monitors for open and short circuit faults along the cable ensuring notification if the cable becomes
damaged.It is fitted with its own internal temperature monitor and should the temperature within the controller enclosure reach 100°C (212°F), an alarm will be signaled.
Each control unit may have up to 500m (1640ft) of LHD sensor cable connected to it, acting as a single detection zone. When the LHD sensor cable and the control unit are installed in different areas, a suitable interposing cable can be used to make the electrical connection between them.
FEATURES & BENEFITS
- UL521 and CE approval, UL/ULC listed
- Up to 500m of sensor cable per zone
- Separate pre-alarm and alarm signals
- Easy programmable interface
- Enclosure temperature alarm
- IP66 rated enclosure
- No nomograms or charts required
Other Reference : ProReact A1163
Recently Viewed
R1234ZE Gas Detector GDR453S10
R-1234ze refrigerant Gas Detector, HFO-1234ze Gas Detector 0-1000 PPM 4-20mA Relay, Display & Buzzer - Semiconductor sensor, for non classified area GDR453S10 - Tecnocontrol
R1234YF Gas Detector GDR400S11
R-1234yf refrigerant Gas Detector, HFO-1234yf Gas Detector 0-1000 PPM 4-20mA Relay & Buzzer - Semiconductor sensor, for non classified area GDR400S11 - Tecnocontrol
R1234YF Gas Detector GDR453I11
R-1234yf refrigerant Gas Detector, HFO-1234yf Gas Detector 0-2000 PPM 4-20mA Relay, Display & Buzzer - Infrared sensor, for non classified area GDR453I11 - Tecnocontrol
R1234YF Gas Detector GDR403I11
R-1234yf refrigerant Gas Detector, HFO-1234yf Gas Detector 0-2000 PPM 4-20mA Relay & Buzzer - Infrared sensor, for non classified area GDR403I11 - Tecnocontrol
R1234YF Gas Detector GDR300S11
R-1234yf refrigerant Gas Detector, HFO-1234yf Gas Detector 0-1000 PPM 4-20mA - Semiconductor sensor, for non classified area GDR300S11 - Tecnocontrol
R1234YF Gas Detector GDR453S11
R-1234yf refrigerant Gas Detector, HFO-1234yf Gas Detector 0-1000 PPM 4-20mA Relay, Display & Buzzer - Semiconductor sensor, for non classified area GDR453S11 - Tecnocontrol
R1234YF Gas Detector GDR403S11
R-1234yf refrigerant Gas Detector, HFO-1234yf Gas Detector 0-1000 PPM 4-20mA Relay & Buzzer - Semiconductor sensor, for non classified area GDR403S11 - Tecnocontrol
Solo A5 Smoke Detector Test Gas Canister 250ml (Flammable) - SOLOA5-001 - No Climb
Carbon Monoxide Detector Tester SOLOC3-001 - No Climb products
Optical and acoustical Remote Indicator AI673
Optical and acoustical Remote Indicator, Low current consumption - AI673 UTC Fire & Security
English (UK)
Français (FR)