S2097AB Détecteur de Gaz Acétate de Butyle, AcOnBu, Butyl Acetate Gas DetectorS2097AB Détecteur de Gaz Acétate de Butyle, AcOnBu, Butyl Acetate Gas Detector
S2097AB Détecteur de Gaz Acétate de Butyle, AcOnBu, Butyl Acetate Gas Detector
S2097AB Détecteur de Gaz Acétate de Butyle, AcOnBu, Butyl Acetate Gas Detector

Butyl Acetate Gas Detector - Explosion Proof Enclosure Version S2097AB

Butyl Acetate Gas Detector, AcOnBu Gas Detector 0-100% LEL 4-20mA - Catalytic sensor - SMART3G-C2 Sensitron Explosion Proof Enclosure version Zone 1 category 2 areas S2097AB
Description

S2097AB - BUTYL ACETATE Gas Detector 0-100% LEL, 4-20mA - Catalytic sensor - Explosion Proof Enclosure Version SMART3G-C2 Zone 1 category 2 areas

S2097AB SMART3G gas detectors are employed to detect Butyl Acetate, AcOnBu compounds (%LEL) in classified areas.
The Pellistor sensors employed for the flammable Gas detection show an excellent output linearity up to 100% LEL.
The SMART3G line has been designed to offer a wide range of alternatives that grant customers the best solution to their requirements.
SMART3G-C has been specifically designed to offer high performance products for industrial applications.
SMART3G detectors are ATEX certified for:
Group II 2G, 2GD, 3G & GD
Group I M2
SMART3G detectors are SIL2 HW TUV certified

FEATURES & BENEFITS

- Easy sensor replacement
- Wide range of sensors and detectable gases
- Standard 4-20 mA 3 wires output
- Wide range of accessories for installation and maintenance
- Zero tracking and system self diagnosis
- ATEX certified Group I & II

APPLICATION

- Refineries
- Compressor stations
- Pharmaceutical plants
- Petrochemical Plants
- Gas turbines
- LNG/LPG storage facilities
- Laboratories
- Tunnels and mines

TECHNICAL SPECIFICATIONS

  • Gas Detector type : Butyl Acetate Gas Detector, AcOnBu Gas Detector
  • Sensing element : Catalytic sensor
  • Measuring range : %LEL
  • Power supply : 12-24Vdc -20% +15%
  • Consumption at 12Vdc : 90mA (medium); 130mA (max)
  • Visual indications : flickering LED
  • Proportional output : 4-20 mA (200 O)
  • Serial Output (optional) : RS 485 and proprietary protocol for addressable gas control panel
  • Relay outputs, with mode status LEDs (optional) : 3 relays with tension free changeover. contact 24V-1A
  • Accuracy : from ©2% to ©5% FS (depending on sensor type)
  • Repeatability : from ©2% to ©5% FS (depending on sensor type)
  • Warm-up time : 5 minutes
  • Stabilization time : < 2 minutes
  • Response time T90 : From 15 to 30 sec. (depending on sensor type)
  • Storage temperature : -25°C to +60°C
  • Operating temperature : -40°C to +60°C (+65°C or 75°C on request) Always refer to the detector's label
  • Relative humidity : 20-90% RH / 40°C (5-95% RH non condensing on request)
  • IP rating : IP 65
  • Operative pressure : 80-110 KPa
  • Max. air velocity : 6 m/s
  • Weight : 950-1700 g
  • Dimension (approx) L.130 H.180 D.90 mm
  • Orientation : Detector must be mounted sensor head downwards
  • Certificates : CESI 01 ATEX 053, CESI 02 ATEX 084 (Performance)
  • EMC Reference Norms : EN 50270: 2011, EN 61000

 

Our Services

Ordering

Delivery options

Payment methods

After-sales Services

 

 

Help

Search a Product

Contact Us

Sitemap

Conditions of Special Offers

 

 

Ornicom Security products

© 1989 - 2016 Ornicom All Rights Reserved.
 
5550 Alle-sur-Semois Belgium
Tel:+32 61 48 01 50
Fax:+32 61 48 01 51
E-mail: This email address is being protected from spambots. You need JavaScript enabled to view it.
 
Payment methods
SSL