The Sigma CP range consists of a series of conventional fire detection alarm system panel designed in accordance with European standards BS EN54-2 and BS EN54-4 Fire Detection and Fire Alarm systems - Control and Indicating Equipment.
The range consists of 2, 4 and 8 zone fire detection alarm system panel.
Sigma T11 range in which detectors, call points and sounders are wired to the same pair of cables. Commonly referred to as a two-wire system.
Wiring sounders to the detection circuit eliminates the need to install sounder circuit cables and also offers the ability to provide zoned or two stage sounder operation.
Notes : For 2-wire T series panels, compatible detectors and call points must be used. All sounders must be polarised.
All fire detection alarm system panel have an integral, mains powered battery charger and power supply designed in accordance with the requirements of BS EN54-4.
FEATURES & BENEFITS
- Fully certified to BS EN54-2 and BS EN54-4
- 2-wire Versions in 2, 4 or 8 zones
- Compatible for use on BS5839: Part 1: 2002 installations
- 2-wire repeaters and ancillary boards
- Fully programmable using simple menu options
- Adjustable sounder delay time
- Sounder configuration options
- Zonal sounder delay detectors only
- Zonal sounder delay call points only
- Coincidence input selection
- I.S Barrier selection by zone
- Short circuit fire by zone
- Non latching zones
- Silent zones
- Zone input delay
- General panel configuration
- Simple, single board construction
- Installer friendly
- Compatible with wide range of fire detection devices
- 3 Amp power supply
- Auxiliary power output
TECHNICAL SPECIFICATIONS
- Construction : 1.2 mm mild sheet steel
- Finish : Epoxy powder coated
- Colour - lid & box : BS 00 A 05 grey - fine texture
- Colour - control plate & labels : RAL 7047 light grey - satin
- Supply voltage : 230 VAC (+10%/-15%)
- Mains supply fuse : 1.6 A 250V
- Power supply DC rating : 24V 3A
- Maximum battery size : 7Ah 12V (2 per panel)
- Fault contact rating : 30 VDC 1A
- Local fire contact rating : 30 VDC 1A
- Fire contact rating : 30 VDC 1A
- Sounder output rating : 0.5A per output (Max 1.6A over all outputs)
- Detection zone current : 1.6 mA
- Detection zone EOL resistor : 6K8 5%
- Active EOL : K14606K (optional)
- Sounder output EOL resistor : 10K 5%
- Cable capacity : 2.5 mm©
- Operating temperature : -5°C a +50°C
- Operating humidity : < 95% (non condensing)
- Dimension : 385 mm x 310 mm x 90 mm
- Standby current 2 zones : 0.065 A
- Standby current 4 zones : 0.075 A
- Standby current 8 zones : 0.093 A
- Alarm current 2 zones : 0.15 A
- Alarm current 4 zones : 0.30 A
- Alarm current 8 zones : 0.63 A
Recently Viewed
Indoor siren, 1 tone - without flash AS270 UTC Fire & Security Aritech
1.3MP HD Network Speed Dome DS-2DE5174
1.3MP HD Network Speed Dome DS-2DE5174 series - HIKVISION
Scorpion Point Detector Head Unit Kit SCORP1001-001 No Climb products
2MP HD Network Speed Dome DS-2DE5186
2MP HD Network Speed Dome DS-2DE5186 series - HIKVISION
2 Zones Conventional Fire Alarm Panel HRZ2 Morley-IAS
Carbon Dioxide Gas Detector - Explosion Proof Enclosure Version S2634CO2
Carbon Dioxide Gas Detector, CO2 Gas Detector 0-2% Vol 4-20mA - Infrared sensor SMART3G-D2 Sensitron Explosion Proof Enclosure Version with display Zone 1 Category 2 areas S2634CO2
Ethane Gas Detector - Explosion Proof Enclosure Version S2157EN
Ethane Gas Detector, C2H6 Gas Detector 0-100% LFL 4-20mA - Catalytic sensor - SMART3G-D2 Sensitron Explosion Proof Enclosure Version with display Zone 1 category 2 areas S2157EN
8 inch Fire bell for outdoor use, EN54-3 Approved, 24 VDC - AB380E UTC Fire & Security
Home Systems Audio Board with X-10 CS534 UTC Fire & Security Aritech
English (UK)
Français (FR)