Tableau répétiteur Marine 12 zones conventionnelles ESEN-12MAR
Tableau répétiteur agréé Marine 12 zones conventionnelles ESEN-R-12MAR - HAES
ESEN-R-12MAR - Tableau Répétiteur agréé Marine 12 zones conventionnelles - HAES
The Esento Marine repeater panel has the same, easy to use, controls and indications as the main control panel but mounted in a smaller cabinet. The repeaters are fully functional with ‘Silence’, ‘Resound’ and ‘Reset’ controls, as well as Disable and Test Mode functions. It is also possible to disable the controls for each or all repeater panels to make them passive (indication only). Up to 8 repeater panels can be supported on a Esento Marine 8-12 zone system.
Repeater panels are designed to be wired in a fault tolerant (fail safe) loop configuration, from comms A to B and back to the main panel again. This enables repeater panels to still work if there is a break in the cables. If replacing an older system where the existing cabling cannot be configured in a loop as above, it is possible to re-programme the panel back to legacy RS485 circuit comms monitoring. This then allows any topology of comms cabling to be utilised.
The main circuit board has 2, switch –ve, inputs which can be used to sound or pulse the alarms. These inputs can also be re-programmed for use as PSU fault inputs. The internal comms PCB has 6, switch –ve, programmable outputs. Different key types are used for the door lock and the ‘activate controls’ key-switch. It is also possible to enable the controls via a 4 digit code entry if preferred. An eight button keypad is used to control the system and allow access to the function options (unless disabled).
The control panel comprises of a sheet steel enclosure suitable for wall mounting with a hinged, lockable front access door. It can be semi recessed, using a suitable recessing bezel. Cable entry is via 20mm ‘knockouts’ located at the top and rear of the cabinet. The battery compartment also includes a secure battery clamp.
The repeaters are supplied with a 1.5 amp internal power supply module. This module complies with the requirements of EN54-4 : 1988 and provides temperature compensated battery management charging.
Esento Marine panels are approved by the BRE which is a Notified Body authorised by the MCA to Modules B & D, Lloyds Register and the American Bureau of Shipping
Available in Grey or Black
FEATURES & BENEFITS
- Same easy-to-use controls and indications as panel
- Can be fully functional or passive
- 12 zonal fire & fault indications
- Integral 1.25 Amp PSU
- Class change & alert inputs
- Test mode and disablement functions
- 6 programmable switch -ve outputs
- Fault tolerant loop or legacy radial wiring options
- 12 month warranty
Produits consultés
Diffuseur sonore, EEx d IIC T4, 24Vdc, 250mA, 32 tons, IP67, 117dBA AS374
Diffuseur sonore, EEx d IIC T4, 24Vdc, 250mA, 32 tons, IP67, 117dBA, boîtier en aluminium anodisé qualité Marine, IP67 - AS374 UTC Fire & Security
Centrale Gaz 256 Zones Multiscan S1 STMTSS1
Centrale Détection Gaz 256 zones ATEX et SIL1 Rack 19" Multiscan++S1 Sensitron STMTS/S1
Centrale Gaz 64 Zones Multiscan S1 STMTSS1-64B
Centrale Détection Gaz 64 zones ATEX et SIL1 boitier ABS IP65 Multiscan++S1 Sensitron STMTS/S1-64B
Centrale Gaz 32 Zones Multiscan S1 STMTSS1-32B
Centrale Détection Gaz 32 zones ATEX et SIL1 boitier ABS IP65 Multiscan++S1 Sensitron STMTS/S1-32B
Socle de montage avec Isolateur YBN-R/3(SCI)/SIL
Socle de montage avec Isolateur, Ivoire, agréé SIL2 YBN-R/3(SCI)/SIL - Hochiki
Centrale Gaz 16 Zones Multiscan S1 STMTSS1-16B
Centrale Détection Gaz 16 zones ATEX et SIL1 boitier ABS IP65 Multiscan++S1 Sensitron STMTS/S1-16B
Français (FR)
English (UK)