Detecteur de Flamme UV 40-40UB
Detecteur de Flamme UV avec testeur intégré boitier antidéflagrant 40/40U SharpEye SPECTREX
40/40UB - Détecteur de Flamme UV avec testeur intégré - Boitier antidéflagrant SharpEye Spectrex
The new 40/40 UV Flame Detector detects hydrocarbon-based fuel and gas fires, invisible hydrogen flames, and fires from hydrides, ammonia, silane and other organics. The 40/40U-UB is the most durable and weather resistant UV flame detector currently on the market. Its new features include a heated window, to eliminate condensation and icing; HART capabilities, for digital communications; lower power requirements; and a compact, lighter design.
Due to increased reliability, the 40/40 Series warranty period has been extended to 5 years and is SIL2 (TUV) approved to IEC 61508.
The model 40/40UB includes a Built-in-Test (BIT) feature, whereas the 40/40U model does not.
Note: This type of detector should not be exposed to UV radiation sources such as welding, sparks, and electric arcs as it will cause false alarms.
Boitier standard : Aluminium (Boitier Inoxydable en option)
FEATURES & BENEFITS
- UV spectrum design
- 3 seconds response
- Automatic and Manual Built-In-Test (BIT) - to assure continued reliable operation
- Heated window - for operation in harsh weather conditions (snow, ice, condensation)
- Multiple output options for maximum flexibility and compatibility: - Relays (3) for Alarm, Fault and Auxiliary - 0-20mA (stepped) - HART Protocol for maintenance and asset management - RS-485, Modbus Compatible
- High Reliability - MTBF - minimum 150,000 hours
- Approved to Safety Integrity Level 2 (SIL2 – TUV) Model 40/40UB only
- 5-Year Warranty
- User Programmable via HART or RS-485
- Ex approved for Zone 1 hazardous area location : - ATEX - IECEx - FM/FMC - CSA
- 3rd party Performance Tested : - EN54-10 (LPCB) - FM3260 (FM)
APPLICATIONS
- Chemical plants
- Petrochemicals plants
- Power Generation facilities
- Pharmaceutical Industry
- Printing Industry
- Warehouses
- Automotive Industry
- Aerospace
- Explosives & Munitions
- Waste Disposal facilities
- Paint and solvent processes
GENERAL SPECIFICATIONS
- Spectral Response : UV 0.185-0.260 μm
- Detection Range : n-Heptane 15m, Ethanol 95% 11m, LPG 12m, Gasoline 15m, Methanol 11m, Polypropylene Pellets 5m, Diesel Fuel 11m, IPA (Isopropyl Alcohol) 11m, Office Paper 6m, JP5 11m, Hydrogen 10m, Kerosene 11m, Methane 12m
- Response Time Typically : 3 seconds
- Adjustable Time Delay : Up to 30 seconds
- Sensitivity Ranges : 0.1m2 n-heptane pan fire from 15m
- Field of View : Horizontal 100º; Vertical 95º
- Built-in-Test (BIT) : Automatic (and Manual)
- Temperature Range : Operating: -55ºC to +75ºC, Option: -55ºC to +85ºC, Storage: -55ºC to +85ºC
- Humidity : Up to 95% non-condensing (withstands up to 100% RH for short periods)
- Heated Optics : To eliminate condensation and icing on the window
ELECTRICAL SPECIFICATIONS
- Operating Voltage : 24 VDC nominal (18-32 VDC)
- Power Consumption : Standby: Max. 90mA (110mA with heated window), Alarm: Max. 130mA (160mA with heated window)
- Cable Entries : 2 x 3/4" - 14NPT conduits or 2 x M25 x 1.5 mm ISO
- Wiring : 12 - 22AWG (2.5mm2 - 0.3mm2)
- Electrical Input Protection : According to MIL-STD-1275B
- Electromagnetic Compatibility : EMI/RFI protected to EN61326-3 and EN61000-6-3
- Electrical Interface : The detector includes twelve (12) terminals with five (5) wiring options (factory set)
OUTPUTS
- Relays : Alarm, Fault and Auxiliary, SPST volt-free contacts rated 5A at 30 VDC or 250 VAC.
- 0-20mA (stepped) : Sink (source option) configuration, Fault: 0 +1mA, Warning: 16mA ± 5%, BIT Fault: 2mA ± 10%, Alarm: 20mA ± 5%, Normal: 4mA ± 10%, Resistance Loop: 100-600 Ω
- HART Protocol : Optional HART communications on the 0-20mA analog current (FSK) - used for maintenance, configuration changes and asset management, available in mA source output wiring options
- RS-485 : RS-485 Modbus compatible communication link that can be used in computer controlled installations
MECHANICAL SPECIFICATIONS
- Materials : - Stainless Steel 316L with electro polish finish, Enclosure options - Heavy duty copper free aluminum (less than 1%), red epoxy enamel finish
- Mounting : Stainless Steel 316L with electro polish finish
- Dimensions Detector : 101.6 x 117 x 157 mm
- Weight : Detector : 2.8 kg, Tilt mount : 1.0 kg, Detector, aluminum : 1.3 kg
- Environmental Standards : Meets MIL-STD-810C for Humidity, Salt & Fog, Vibration, Mechanical Shock, High Temp, Low Temp
- Water and Dust I: P66 and IP67 per EN60529, NEMA 250 6P
APPROVALS
- Hazardous Area : ATEX and IECEx Ex II 2 GD, Ex de IIC T5 (-55ºC to +75ºC) Ex de IIC T4 (-55ºC to +85ºC), Ex tD A21 IP66/X7 T 95ºC Ex tD A21 IP66/X7 T 105ºC, FM/FMC/CSA Class I Div. 1, Groups B, C & D, Class II/III Div. 1, Groups E, F & G
- Performance : EN54-10 (LPCB), FM-3260 (FM)
- Reliability : IEC61508 - SIL2 (TUV) - model 40/40UB only