Laser Air-sampling Smoke Detector with 2 inlets

Laser Air-sampling Smoke Detector with 2 inlets ICAM by Xtralis
Description

ILS-2 - Laser Air-sampling Smoke Detector with 2 inlets ICAM

The ICAM ILS systems provide Laser Air-sampling Smoke Detection solutions to meet the unique needs of numerous commercial and industrial applications. ILS systems are suitable for both medium sensitivity and multihole Class C applications.

How it Works
The ILS systems actively draw air from the protected area through sampling holes in a pipe network. Sampled air is then filtered before being analyzed by medium sensitivity laser spot (point) detectors incorporated in the systems.
Alarm states (Alert, Action or Fire) are reported by activating functional LEDs in the display and dry contact relays.
The systems utilize a high performance aspirator and software configurable flow monitoring circuitry. Air flow is displayed on a ten element bar graph that can be adjusted for high and low flow thresholds, and flow failure is reported as a device fault via dedicated fault relays.

Programming & Diagnostics
The sensitivity thresholds for each of the three alarm levels, fan speed and flow sensitivity can be individually programmed. A USB interface provides a connection to a PC for system configuration. The ILS system can also be locally configured through an integrated programming interface.

FEATURES & BENEFITS

- Dual channel smoke detection
- Laser air-sampling smoke detection
- Multiple detection strategies
- 100 m (328 ft) per sampling pipe
- Microprocessor controlled and programmed
- Highest fan capacity in its class
- Integral display and programmer
- Field serviceable air filter
- Adjustable aspirator speed with airflow monitoring
- IP65 enclosure

DETECTION STRATEGIES

The ILS-2 is fitted with two detectors per system, it can be configured for a number of detection strategies.

Possible detection strategies for ILS-2 :
- Dual addressable areas
- Coincident / Double-Knock (AND) *
* Subject to local codes and standards.
Note: (AND) represents the boolean logic for combining two detectors to achieve detection strategy.

LISTINGS/APPROVALS

Equipment Approvals:
- EN54-20 (VdS)
- CE EMC
- CPD
- EN54-20 Sensitivity (holes per pipe)
- Class A - 3 holes
- Class B - 6 holes
- Class C - 18 holes
Factory Approvals:
- VdS

TECHNICAL SPECIFICATIONS

  • Integrated detectors : 2 laser spot (point) detectors
  • Supply Voltage : 24 VDC nominal (18 to 30 VDC)
  • Current : 300 mA (max)
  • Dimensions (WHD) : 259 mm x 184 mm x 166 mm (10.2 in. x 7.2 in. x 6.5 in.)
  • Operating Conditions : Temperature: -10 to 50 °C (14 to 122 ©F)
  • Humidity : 10 to 95% RH (noncondensing)
  • Inlet Pipe Size : Outer Diameter: 25 mm (1 in.), Inner Diameter: 21 mm (0.8 in.)
  • Sampling Network : Pipe Length: 100 m (328 ft.) per inlet
  • Sensitivity : 0.06 to 6.0 % obs/m (0.02 to 1.83 % obs/ft)
  • IP Rating : IP65
  • Filtration : Serviceable filter, External filter optional
  • Flow Monitoring and Reporting : High and Low adjustable
  • Fan Control : 10 programmable speeds
  • Relays : Contacts rated at 1A @ 30 VDC, NO/NC
  • 3 relays : Action, Fire, Fault
  • Cable Termination Power Supply : 18 AWG min. (16 x 0.25 mm dia.)
  • Cable Termination Field Connections : 11 AWG max. (2.5 mm dia.)
  • USB : Standard USB cable for Type B USB connector

-


A question ?

Worldwide Shipping

Short About Us

Ornicom leans on more than 30 years of experience to propose a large and innovative range of safety integrated system.

By bringing a personalized answer to their specific problems, we accompany our customers, stage after stage, towards the success of their projects.

Find Out More

Our customers

Need a Catalog ?

Our Services

Ordering

Delivery options

Payment methods

After-sales Services

 

 

Help

Search a Product

Contact Us

Sitemap

Conditions of Special Offers

 

 

 

Ornicom Security products

© 1989 - 2023 Ornicom All Rights Reserved.
 
6830 Bouillon, Belgium
Tel:+32 477 23 76 79
Fax:+32 61 48 01 51
E-mail: This email address is being protected from spambots. You need JavaScript enabled to view it.
 
Payment methods
JUMP TO TOP